Treatment of cooling tower blowdown water by using adsorption-electrocatalytic oxidation: Technical performance, toxicity assessment and economic evaluation

  • Xiaoliang Li
  • , Linjie Wu
  • , Sijia Lu
  • , Heyun Yang
  • , Wenzhou Xie
  • , Huiyan Zhao
  • , Yaozhong Zhang
  • , Xin Cao
  • , Gang Tang
  • , Hesheng Li
  • , Jiangtao Feng
  • , Wei Yan
  • , Xing Zheng
  • Xi'an University of Technology
  • Xi'an Municipal Engineering Design & Research Institute Co., Ltd.
  • Beijing Research Institute of Coal Chemistry
  • SINOPEC
  • Southern University of Science and Technology

科研成果: 期刊稿件文章同行评审

20 引用 (Scopus)

摘要

An eco-friendly process was adopted to treat cooling tower blowdown water (CTBD) and the toxicity of correspondingly produced water/eluate was evaluated using the transcriptional effect level index (TELI) based on toxicogenomics. The objective of the work is to provide a feasible treatment loop including adsorption to remove organics and phosphorus from CTBD, electrocatalytic oxidation to improve the biodegradability of the eluate after desorption. Results showed that PANI/TiO2 was a promising adsorbent in the removal of organics and phosphorus from CTBD and exhibited a satisfied regeneration ability beyond 30 times of reuse. During the electrocatalytic oxidation process the biodegradability of desorption eluate was gradually increasing and BOD5/COD of the oxidized eluate reached 0.4 after 4.8 h of treatment, indicating that the treated wastewater could be returned to the biological treatment loop for further processing. The analysis of the quantitative toxicogenomics assay revealed that the toxicity of CTBD was mainly caused by oxidizing biocides of trichloroisocyanuric acid (TCCA), leading to a significant membrane stress response of bacteria. And the toxicity level of CTBD decreased after adsorption treatment while the desorption eluate experienced increase and then decrease during the electrocatalytic oxidation, meaning that certain oxidation duration was needed to keep the eluate safe for biological treatment. According to economic analysis, the operation cost of treatment loop was estimated at around 0.6 dollars/m3, ensuring high reuse water quality and safe eluate for further biological treatment.

源语言英语
文章编号117484
期刊Separation and Purification Technology
252
DOI
出版状态已出版 - 1 12月 2020