跳到主要导航 跳到搜索 跳到主要内容

Thermal modeling for the motor in semi-hermetic screw refrigeration compressors under part-load conditions

  • Wenqing Chen
  • , Ziwen Xing
  • , Jiubing Shen
  • , Zhilong He
  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

11 引用 (Scopus)

摘要

In the semi-hermetic screw refrigeration compressor, the motor is mostly cooled down by suction refrigerant before it flows into the compressor suction port. To investigate cooling effects of the motor and performance of the compressor under part-load conditions, a lumped parameter model describing heat-transfer characteristics inside the motor and a part-load model of screw refrigeration compressor are developed and validated. Heating effects at compressor suction end and heat conduction from the male rotor screw to the motor shaft are taken into account. Nodes representing refrigerant inside the motor cooling passages are modeled separately. Temperature rise of refrigerant through the motor increases when the compressor load drops by either suction volume variation or speed variation. With drop of the compressor load, stator winding temperature goes up in the case of suction volume variation by slide valve motion, but it lows in the case of speed variation by frequency conversion.

源语言英语
页(从-至)1874-1882
页数9
期刊International Journal of Refrigeration
卷36
期7
DOI
出版状态已出版 - 11月 2013

学术指纹

探究 'Thermal modeling for the motor in semi-hermetic screw refrigeration compressors under part-load conditions' 的科研主题。它们共同构成独一无二的学术指纹。

引用此