摘要
The ejector refrigeration integrated in the air-conditioning system is a promising technology, because it could be driven by the low grade energy. In the present study, a theoretical calculation based on the real gas property is put forward to estimate the ejector refrigeration system performance under overall modes (critical/sub-critical modes). The experimental data from literature are applied to validate the proposed model. The findings show that the proposed model has higher accuracy compared to the model using the ideal gas law, especially when the ejector operates at sub-critical mode. Then, the performances of the ejector refrigeration circle using different refrigerants are analyzed. R290 and R134a are selected as typical refrigerants by considering the aspects of COP, environmental impact, safety and economy. Finally, the ejector refrigeration performance is investigated under variable operation conditions with R290 and R134a as refrigerants. The results show that the R290 ejector circle has higher COP under critical mode and could operate at low evaporator temperature. However, the performance would decrease rapidly at high condenser temperature. The performance of R134a ejector circle is the opposite, with relatively lower COP, and higher COP at high condenser temperature compared to R290.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 2074-2084 |
| 页数 | 11 |
| 期刊 | Applied Energy |
| 卷 | 185 |
| DOI | |
| 出版状态 | 已出版 - 1 1月 2017 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源