跳到主要导航 跳到搜索 跳到主要内容

The dynamic load adjustment of power transformers based on the inner temperature

  • Xi'an Jiaotong University
  • ABB Group

科研成果: 书/报告/会议事项章节会议稿件同行评审

3 引用 (Scopus)

摘要

The inner temperature of power transformers is one of the major factors of the life of insulation life and the load operation mode in transformers. So it's of great significance to predict and calculate the inner temperature of transformers precisely in different loads and ambient temperature, which could be used to assess the surplus useful life and the safety performance of transformers. When the inner temperature of transformers is too low, it's evident that the load capacities of the power transformers are in half-load or less, which might reduce the economic benefit. However, when the inner temperature of transformers is too high, Not only do the ageing rating of insulation structure in power transformers is accelerated, but also the dielectric loss angle because of the aging products, which could prompt the inner temperature in power transformers higher. As a result, the remaining useful life of power transformers is decreased, and all kinds of partial discharge might happen for the degradation of the insulation structure in power transformers. Therefore, in order to make a balance between an integral remaining life of transformers and economical benefits, it's necessary to predict, calculate and monitor the inner temperature of power transformers, which could guarantee the operation mode safely and economically in some certain circumstance. In this paper, the influence of the inner temperature of transformers to the aging of insulation structure is first introduced. Then the relationship between the inner temperature of transformers and load in summer and winter is analyzed by thermal circuit model, from which we obtained the top-oil temperature of a certain transformer in different ambient temperature. And the data we measured shows that there is certain accuracy of the data we calculated by using thermal circuit model, and the maximum error between the data we calculated and measured is lower than 5°C. So there is a convenient way to estimate the inner temperature of transformers and guide the model of lifting loads. Besides, in the premise of remaining life and normal operation of transformers, the estimation of the inner temperature of transformers could be used to prompt economic performance.

源语言英语
主期刊名CMD 2016 - International Conference on Condition Monitoring and Diagnosis
出版商Institute of Electrical and Electronics Engineers Inc.
790-793
页数4
ISBN(电子版)9781509033980
DOI
出版状态已出版 - 28 11月 2016
活动2016 International Conference on Condition Monitoring and Diagnosis, CMD 2016 - Xi'an, 中国
期限: 25 9月 201628 9月 2016

出版系列

姓名CMD 2016 - International Conference on Condition Monitoring and Diagnosis

会议

会议2016 International Conference on Condition Monitoring and Diagnosis, CMD 2016
国家/地区中国
Xi'an
时期25/09/1628/09/16

学术指纹

探究 'The dynamic load adjustment of power transformers based on the inner temperature' 的科研主题。它们共同构成独一无二的指纹。

引用此