摘要
A liquid desiccant-indirect evaporative cooling (LD-IEC) system has been proposed. The design is able to dehumidify and cool the product air simultaneously in one unit. A computational model has been developed to determine the performance of the heat and mass transfer process. The validation of the model demonstrated good agreement with the experimental data to within 10%. The detailed air treatment process has been theoretically studied. The thermal performance of the LD-IEC has been evaluated. Simulation results showed that the outlet temperature and humidity ratio were influenced by the liquid desiccant film length, intake air temperature, and intake air humidity ratio. For a specific inlet temperature and humidity ratio condition, a desired outlet condition can be obtained by adjusting the length of the liquid desiccant film.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 5659-5665 |
| 页数 | 7 |
| 期刊 | Energy Procedia |
| 卷 | 158 |
| DOI | |
| 出版状态 | 已出版 - 2019 |
| 活动 | 10th International Conference on Applied Energy, ICAE 2018 - Hong Kong, 中国 期限: 22 8月 2018 → 25 8月 2018 |
学术指纹
探究 'Studying the performance of a liquid desiccant indirect evaporative cooling system' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver