跳到主要导航 跳到搜索 跳到主要内容

Study on the Dielectric Recovery Performance of High Voltage SF6 Circuit Breaker

  • China Southern Power Grid
  • Xi'an Jiaotong University

科研成果: 书/报告/会议事项章节会议稿件同行评审

4 引用 (Scopus)

摘要

To investigate the dielectric recovery performance of the SF6 circuit breaker after the current zero (CZ), the magneto-hydro-dynamic (MHD) model of arc burning process was established for the structure of a 126 kV auto-expansion switch. Two methods of evaluating the post-arc dielectric recovery strength were established. The fist method is predicting the most likely area of post-arc electric breakdown according to the temperature and pressure distribution. Another method is based on the leader inception criterion. The results about the post-arc breakdown voltage and electrical field distribution is essential for the evaluation of the performance of arc interruption. The simulation results can be used to estimate the possibility of breakdown and arc reburning after CZ. The influence of current value on the strength recovery during the post-arc is studied. It is indicated that higher current is conducive to the post-arc dielectric recovery. The results of this paper are significant for the optimization design of high voltage circuit breaker.

源语言英语
主期刊名2022 IEEE International Conference on High Voltage Engineering and Applications, ICHVE 2022
出版商Institute of Electrical and Electronics Engineers Inc.
ISBN(电子版)9781665407502
DOI
出版状态已出版 - 2022
活动2022 IEEE International Conference on High Voltage Engineering and Applications, ICHVE 2022 - Chongqing, 中国
期限: 25 9月 202229 9月 2022

出版系列

姓名2022 IEEE International Conference on High Voltage Engineering and Applications, ICHVE 2022

会议

会议2022 IEEE International Conference on High Voltage Engineering and Applications, ICHVE 2022
国家/地区中国
Chongqing
时期25/09/2229/09/22

学术指纹

探究 'Study on the Dielectric Recovery Performance of High Voltage SF6 Circuit Breaker' 的科研主题。它们共同构成独一无二的学术指纹。

引用此