跳到主要导航 跳到搜索 跳到主要内容

Study on temperature measurement and controlling of liquid metal LiPb loop for fusion reactor

  • Zhi Qiang Zhu
  • , Sheng Gao
  • , Mao Lian Zhang
  • , Qun Ying Huang
  • , Yi Can Wu
  • , You Bin Xu
  • CAS - Institute of Plasma Physics
  • Hefei Yikong Science and Technology Co. LTD.

科研成果: 期刊稿件文章同行评审

1 引用 (Scopus)

摘要

Liquid metal LiPb loop is considered as the unique testing facility to research the technology of liquid metal blanket for fusion reactor. In order to get the proper method of temperature measurement and controlling for high temperature LiPb in loops, 316L pipe is chosen to be heated up, and a temperature controlling system is designed so as to test the K-type thermal couples with different working styles. It is found that the temperatures of naked-type of thermal couples are much closer to the set-up temperature than those of shell-type or insulation-type ones at the same cross-section of the pipe, and the fluctuation of those temperature curves are very small. So, naked-type thermal couples are chosen to be used in DRAGON-I loop, the first thermal convection liquid metal LiPb loop in China. And the temperature measurement and controlling system satisfy well the need of temperature measurement for LiPb loop.

源语言英语
页(从-至)240-243
页数4
期刊Jiliang Xuebao/Acta Metrologica Sinica
28
SUPPL.
出版状态已出版 - 9月 2007

学术指纹

探究 'Study on temperature measurement and controlling of liquid metal LiPb loop for fusion reactor' 的科研主题。它们共同构成独一无二的学术指纹。

引用此