跳到主要导航 跳到搜索 跳到主要内容

Study on operational tests equivalence and steady-state test method for self-turn-off valves

  • Xiang Luo
  • , Jianchao Zheng
  • , Guangfu Tang
  • , Kunpeng Zha
  • , Zhiyuan He
  • State Grid Corporation of China

科研成果: 期刊稿件文章同行评审

11 引用 (Scopus)

摘要

The equivalence of operational tests for self-turn-off valves was investigated, which contains the test method, the implementation of test method and the analysis of test equivalence. The test method includes identification of test object, valve stresses analysis and establishment of the mathematic models of the stresses, test requirements as well as analysis of test items and equivalent test method. In this paper the steady-state operational test method of voltage-sourced converter based high voltage direct current transmission (VSC-HVDC) valve which are modular multi-level converters (MMC) valves based on IGBT was taken as a example to explain the investigation as to the test method, the test circuit and the equivalence of test, etc. In addition, the accuracy of the equivalent test method is verified.

源语言英语
页(从-至)1-7
页数7
期刊Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
31
3
出版状态已出版 - 25 1月 2011

学术指纹

探究 'Study on operational tests equivalence and steady-state test method for self-turn-off valves' 的科研主题。它们共同构成独一无二的指纹。

引用此