TY - JOUR
T1 - Single-ended active injection for fault location in hybrid MMC-HVDC systems
AU - Song, Guobing
AU - Hou, Junjie
AU - Guo, Bing
AU - Wang, Ting
AU - Masood, Bilal
AU - Kazmi, Sayed Tassawar Hussain
N1 - Publisher Copyright:
© 2020 Elsevier Ltd
PY - 2021/1
Y1 - 2021/1
N2 - The traditional fault location methods on DC lines are facing many challenges such as low reliability and unsatisfied location accuracy. To ensure a more reliable fault recovery of DC line, a single-ended fault location method based on active detection is proposed for hybrid modular multilevel converter based high voltage DC transmission systems. The high controllability of hybrid MMC is utilized to activate the control strategy of injecting a sinusoidal signal. Furthermore, based on parameter identification and compensation methods for the distributed parameter model, the fault location equation with fault impedance parameters is formulated. Finally, the fault location can be identified under different fault scenarios. Simulation results verify the effectiveness and accuracy of the proposed active detection method. The proposed method can pinpoint the fault location with a lower sampling rate, its accuracy is not influenced by increasing of the line length and variation of the fault impedance.
AB - The traditional fault location methods on DC lines are facing many challenges such as low reliability and unsatisfied location accuracy. To ensure a more reliable fault recovery of DC line, a single-ended fault location method based on active detection is proposed for hybrid modular multilevel converter based high voltage DC transmission systems. The high controllability of hybrid MMC is utilized to activate the control strategy of injecting a sinusoidal signal. Furthermore, based on parameter identification and compensation methods for the distributed parameter model, the fault location equation with fault impedance parameters is formulated. Finally, the fault location can be identified under different fault scenarios. Simulation results verify the effectiveness and accuracy of the proposed active detection method. The proposed method can pinpoint the fault location with a lower sampling rate, its accuracy is not influenced by increasing of the line length and variation of the fault impedance.
KW - Active detection
KW - Fault location
KW - Hybrid modular multilevel converter
KW - Parameter identification
KW - Single-ended
UR - https://www.scopus.com/pages/publications/85088049612
U2 - 10.1016/j.ijepes.2020.106344
DO - 10.1016/j.ijepes.2020.106344
M3 - 文章
AN - SCOPUS:85088049612
SN - 0142-0615
VL - 124
JO - International Journal of Electrical Power and Energy Systems
JF - International Journal of Electrical Power and Energy Systems
M1 - 106344
ER -