TY - JOUR
T1 - Simulation and parameters optimization of the resonance fault current limiter resistance
AU - Wang, Huaxin
AU - Xi, Hexun
AU - Tang, Guangfu
AU - Zheng, Jianchao
PY - 2007/3/10
Y1 - 2007/3/10
N2 - The resonance fault current limiter (RFCL) is a practical way to solve the problem of bulk fault current on the EHV. RFCL has the advantage to be able to adapt to complex operations of power grids. The resistance model is built from the main circuit of RFCL in the paper and the parameters affecting the resistance are analyzed. Furthermore, the resonance model is compared with compensated model. From the view of limited current, two parameters of restrain coefficient and resonance coefficient affect the value of the resistance. From the view of system, the negative compensation degree limits the device capability and delivering power under the RFCL fault mode. A large amount of simulation experiments are carried out. The parameters are successfully optimized and electrical strength of the damping circuit is decreased significantly. RFCL has good response to the short circuit current.
AB - The resonance fault current limiter (RFCL) is a practical way to solve the problem of bulk fault current on the EHV. RFCL has the advantage to be able to adapt to complex operations of power grids. The resistance model is built from the main circuit of RFCL in the paper and the parameters affecting the resistance are analyzed. Furthermore, the resonance model is compared with compensated model. From the view of limited current, two parameters of restrain coefficient and resonance coefficient affect the value of the resistance. From the view of system, the negative compensation degree limits the device capability and delivering power under the RFCL fault mode. A large amount of simulation experiments are carried out. The parameters are successfully optimized and electrical strength of the damping circuit is decreased significantly. RFCL has good response to the short circuit current.
KW - Negative compensation degree
KW - Resistance model
KW - Resonance coefficient
KW - Resonance fault current limiter (RFCL)
KW - Restrain coefficient
UR - https://www.scopus.com/pages/publications/34247351655
M3 - 文章
AN - SCOPUS:34247351655
SN - 1000-1026
VL - 31
SP - 61
EP - 64
JO - Dianli Xitong Zidonghua/Automation of Electric Power Systems
JF - Dianli Xitong Zidonghua/Automation of Electric Power Systems
IS - 5
ER -