跳到主要导航 跳到搜索 跳到主要内容

Residual charge distribution of surface leader discharge under positive impulse voltage

  • Junbo Deng
  • , Haibao Mu
  • , Guanjun Zhang
  • , Shigeyasu Matsuoka
  • , Akiko Kumada
  • , Kunihiko Hidaka
  • Xi'an Jiaotong University
  • The University of Tokyo

科研成果: 期刊稿件文章同行评审

27 引用 (Scopus)

摘要

The performance of high-voltage apparatus is seriously restricted by the surface discharge on dielectric materials. A surface charge density distribution scanning system is developed with a dc feedback-type electrostatic probe based on the field-nullifying technique. The residual charge density distribution after the occurrence of a positive leader discharge is measured. Using the 2-D Fourier transformation in the spatial domain and Tikhonov's regularization method, the surface potential distribution and electric field distribution are arrived at. The leader stem and radial lament streamer zone located at the head of the leader can clearly be distinguished from the distributions. There is an obvious knee point that divides the main channel of the discharge into a leader channel and a streamer channel. The knee point is at about 9 kV, which corresponds to about 320 pC mm2.

源语言英语
期刊论文编号6482655
页(从-至)999-1004
页数6
期刊IEEE Transactions on Plasma Science
41
4
DOI
出版状态已出版 - 2013

学术指纹

探究 'Residual charge distribution of surface leader discharge under positive impulse voltage' 的科研主题。它们共同构成独一无二的学术指纹。

引用此