TY - GEN
T1 - Research on Influence of Mechanical Stress on Insulation Characteristics of Oil-immersed Pressboard
AU - Cui, Yanjie
AU - Li, Xining
AU - Zhu, Lingyu
AU - Ji, Shengchang
AU - Zhang, Fan
N1 - Publisher Copyright:
© 2018 IEEE.
PY - 2018/6
Y1 - 2018/6
N2 - Oil-immersed pressboard are used in transformer to separate high voltage winding and low voltage winding, as well as providing structural support. Thus during normal operation of a transformer, oil-immersed pressboard will be subjected to the action of mechanical stress and constantly aging. Moreover, when the transformer suffers a sudden short-circuit, huge axial force will act on the pressboard near winding ends, affecting insulation properties of the pressboard, leading to failure of the transformer. Therefore, it is necessary to study the evolution of insulation properties of oil-impregnated paperboard under different mechanical stress. In this paper, normal mechanical stress experiments on oil-immersed pressboard were performed, and partial discharge tests of insulation pressboard after pressed were carried out in order to obtain its partial discharge inception voltage, breakdown voltage, and partial discharge characteristics. A material testing machine is used to apply mechanical stress between 0 and 100MPa to the pressboard and the strain curve is recorded as well. Insulation characteristics of pressed oil-immersed pressboard were obtained by performing both short-Term and long-Term partial discharge tests under point-plane electrodes. Experimental result indicates that mechanical stress on pressboard will reduce its insulation ability. As the applied mechanical stress increases, the breakdown voltage and withstand voltage time of pressboard will continue to decrease. Partial discharge inception voltage stays substantially when the mechanical stress is relatively low but decreases rapidly when the mechanical stress is higher than 20MPa. When the mechanical stress is higher, the maximum discharge magnitude and average discharge magnitude will be higher, but the distribution phase of discharges has little to do with the mechanical stress.
AB - Oil-immersed pressboard are used in transformer to separate high voltage winding and low voltage winding, as well as providing structural support. Thus during normal operation of a transformer, oil-immersed pressboard will be subjected to the action of mechanical stress and constantly aging. Moreover, when the transformer suffers a sudden short-circuit, huge axial force will act on the pressboard near winding ends, affecting insulation properties of the pressboard, leading to failure of the transformer. Therefore, it is necessary to study the evolution of insulation properties of oil-impregnated paperboard under different mechanical stress. In this paper, normal mechanical stress experiments on oil-immersed pressboard were performed, and partial discharge tests of insulation pressboard after pressed were carried out in order to obtain its partial discharge inception voltage, breakdown voltage, and partial discharge characteristics. A material testing machine is used to apply mechanical stress between 0 and 100MPa to the pressboard and the strain curve is recorded as well. Insulation characteristics of pressed oil-immersed pressboard were obtained by performing both short-Term and long-Term partial discharge tests under point-plane electrodes. Experimental result indicates that mechanical stress on pressboard will reduce its insulation ability. As the applied mechanical stress increases, the breakdown voltage and withstand voltage time of pressboard will continue to decrease. Partial discharge inception voltage stays substantially when the mechanical stress is relatively low but decreases rapidly when the mechanical stress is higher than 20MPa. When the mechanical stress is higher, the maximum discharge magnitude and average discharge magnitude will be higher, but the distribution phase of discharges has little to do with the mechanical stress.
KW - Oil-paper insulation
KW - PRPD patterns
KW - mechanical aging
KW - partial discharge
UR - https://www.scopus.com/pages/publications/85077815923
U2 - 10.1109/IPMHVC.2018.8936841
DO - 10.1109/IPMHVC.2018.8936841
M3 - 会议稿件
AN - SCOPUS:85077815923
T3 - 2018 IEEE International Power Modulator and High Voltage Conference, IPMHVC 2018
SP - 264
EP - 268
BT - 2018 IEEE International Power Modulator and High Voltage Conference, IPMHVC 2018
PB - Institute of Electrical and Electronics Engineers Inc.
T2 - 2018 IEEE International Power Modulator and High Voltage Conference, IPMHVC 2018
Y2 - 3 June 2018 through 7 June 2018
ER -