跳到主要导航 跳到搜索 跳到主要内容

Quantitative assessment of dynamic insulation failure caused by free metallic particles in gas-insulated switchgear under switching transients

  • Shang Gao
  • , Yi Tian
  • , Xinsheng Lu
  • , Bo Niu
  • , Feiyue Ma
  • , Haotian Niu
  • , Yongcan Zhu
  • , Shengtao Li
  • , Licheng Li
  • , Husheng Li
  • Xi'an Polytechnic University
  • Xi'an Jiaotong University
  • Ningxia Electric Power Company
  • China Southern Power Grid
  • University of Tennessee

科研成果: 期刊稿件 › 文章 › 同行评审

摘要

To address the inability of traditional steady-state analysis to reveal transient insulation failure induced by free metallic particles in gas-insulated switchgear (GIS), this paper proposes a quantitative dynamic breakdown risk assessment framework integrating multi-field synergy and non-ideal interfacial collisions. Regarding model development, a Monte Carlo collision model integrating surface micro-morphology and dynamic restitution coefficients is established and validated. It first demonstrates the dynamic evolution of high-density particle accumulation toward high-field triple junctions under the dual excitation of an alternating electric field and mechanical vibration. Regarding evaluation criteria, a dynamic streamer inception criterion is introduced. By extracting the tip-distorted electric field and calculating the effective collisional ionization path integral, a dimensionless K-value is defined as a metric for transient breakdown risk. Based on this framework, two key particle-induced breakdown mechanisms are revealed. First, a competitive size effect is identified: medium-sized particles of approximately 0.6 mm present the highest risk because they combine strong spatial jumping capability with a substantial effective length of electric field distortion. Second, an extreme spatiotemporal coupling effect is uncovered, in which high-K-value particles migrate to high-risk positions during the ultra-short intrusion window of a switching overvoltage peak, creating the most severe condition for insulation failure. This study quantitatively clarifies transient breakdown evolution in GIS over extremely short time scales, fills the theoretical gap in particle-induced failure mechanisms under transient operations, and supports optimal insulation design and operational risk management of critical GIS components.

源语言英语
期刊论文编号111241
期刊Engineering Failure Analysis
卷197
DOI
出版状态已出版 - 1 11月 2026

学术指纹

探究 'Quantitative assessment of dynamic insulation failure caused by free metallic particles in gas-insulated switchgear under switching transients' 的科研主题。它们共同构成独一无二的学术指纹。

引用此