The phenomenon of pressure rise due to arcing faults is the main cause of tank explosion. In this paper, we set up an experimental platform for arcing faults in transformer oil, and analyzed the pressure waveforms by arcing faults spectrally to study the main sources of the high-frequency, mid-frequency and low-frequency components. The main conclusions are as follows: 1) The high-frequency component in the oil pressure waveform was mainly the shock wave and its reflection wave generated during the formation of the arc channel. It was manifested as the “spike” in the early stage of the pressure waveform. 2) The mid-frequency component in the pressure waveform was mainly caused by the rapid change of bubble expansion acceleration. It was manifested as the oscillation part of the pressure waveform. 3) The pressure change caused by the volume compression of transformer oil was the main source of low-frequency component. This low-frequency component was the main component of oil pressure. The findings of this paper are an important reference for the pressure study of arcing faults and the design of tank explosion protection.

源语言英语
主期刊名The Proceedings of the 12th Frontier Academic Forum of Electrical Engineering (FAFEE2025) - Volume IV
编辑Qingxin Yang
出版商Springer Science and Business Media Deutschland GmbH
78-86
页数9
ISBN(印刷版)9789819542819
DOI
出版状态已出版 - 2026
活动12th Frontier Academic Forum of Electrical Engineering, FAFEE 2025 - Xiamen, 中国
期限: 23 5月 202525 5月 2025

出版系列

姓名Lecture Notes in Electrical Engineering
1507 LNEE
ISSN(印刷版)1876-1100
ISSN(电子版)1876-1119

会议

会议12th Frontier Academic Forum of Electrical Engineering, FAFEE 2025
国家/地区中国
Xiamen
时期23/05/2525/05/25

学术指纹

探究 'Pressure Characteristics by Arcing Faults in Transformer Oil' 的科研主题。它们共同构成独一无二的指纹。

引用此