跳到主要导航 跳到搜索 跳到主要内容

Prediction of back pressure on air-cooled unit with effect of ambient wind

  • Weifeng He
  • , Yiping Dai
  • , Qingzhong Ma
  • , Xiaoqiang Niu
  • Xi'an Jiaotong University
  • Shanxi Electricity Science Research Institute

科研成果: 期刊稿件文章同行评审

4 引用 (Scopus)

摘要

A method to predict the operating back pressure for an air-cooled unit was proposed by adding the program for condensation heat transfer between the cold air and steam turbine exhaust in the finned tube exchangers. The performance of the air-cooled unit under windy conditions was simulated, and operating back pressures under different windy speeds and temperatures were predicted with the present method. The result shows that the fan flow rate of the air-cooled unit drops from 476.9 m3/s to 328.6 m3/s when the wind speed increases from 0 m/s to 12 m/s. The heat transfer rate also drops from 15.86 MW to 12.45 MW, and the corresponding operating back pressure rises from 21.5 kPa to 62.5 kPa. In addition, the heat transfer rate drops from 16.36 MW to 15.43 MW and the operating back pressure rises from 12 kPa to 25 kPa when the wind temperature increases from 290 K to 306 K.

源语言英语
页(从-至)15-20
页数6
期刊Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University
45
1
出版状态已出版 - 1月 2011

学术指纹

探究 'Prediction of back pressure on air-cooled unit with effect of ambient wind' 的科研主题。它们共同构成独一无二的学术指纹。

引用此