跳到主要导航 跳到搜索 跳到主要内容

Performance analysis of different high-temperature heat pump systems for low-grade waste heat recovery

  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

120 引用 (Scopus)

摘要

Different heat pump systems were used to recover the heat from waste water with mean temperature of 45 °C and produce hot water with the temperature up to 95°C. Those systems include single-stage vapor compression heat pump (system 1), two-stage heat pump with external heat exchanger (system 2), two-stage heat pump with refrigerant injection (system 3), two-stage heat pump with refrigerant injection and internal heat exchanger (system 4), two-stage heat pump with flash tank (system 5) and two-stage heat pump with flash tank and intercooler (system 6). Thermodynamic and economic analyses were conducted to compare the performance of each system. Results showed that the COP and exergy efficiency for both system 5 and system 6 are quite close, and much higher than those of other systems. Besides, the payback period of both system 5 and system 6 are also shorter as compared to other systems. Considering both the thermodynamic performance and economic quality of the system, system 5 is finally preferred since less initial investment is required for system 5 as compared to system 6.

源语言英语
页(从-至)291-300
页数10
期刊Applied Thermal Engineering
卷71
期1
DOI
出版状态已出版 - 5 10月 2014

学术指纹

探究 'Performance analysis of different high-temperature heat pump systems for low-grade waste heat recovery' 的科研主题。它们共同构成独一无二的学术指纹。

引用此