跳到主要导航 跳到搜索 跳到主要内容

Performance analysis of a counter-flow indirect evaporative cooling system

  • Xin Cui
  • , Guosheng Jia
  • , Yilin Liu
  • , Sicong Zhang
  • , Liwen Jin
  • , Xiangzhao Meng
  • Xi'an Jiaotong University

科研成果: 期刊稿件会议文章同行评审

1 引用 (Scopus)

摘要

A counter-flow regenerative indirect evaporative heat exchanger (RIEHX) was introduced and investigated. This paper aims to conduct an experimental study for the RIEHX to investigate the cooling performance under different operating conditions. The experimental prototype was able to adjust the inlet air flow rate and temperature. The thermal performance of the RIEHX was tested with variable inlet conditions. The experimental results have demonstrated that the supply air can be effectively cooled along the product air flow passages by transferring heat to the wet side of the RIEHX due to water evaporation. Under a constant inlet air velocity, the product air with a higher inlet temperature can obtain a larger temperature reduction. In addition, a lower air flow rate may enhance the cooling effect due to the increased contact duration between the air streams. The proposed system is able to improve the cooling effectiveness of the conventional plate-type indirect evaporative cooler.

源语言英语
文章编号012145
期刊IOP Conference Series: Earth and Environmental Science
268
1
DOI
出版状态已出版 - 2 7月 2019
活动International Conference on Sustainable Energy and Green Technology 2018, SEGT 2018 - Kuala Lumpur, 马来西亚
期限: 11 12月 201814 12月 2018

学术指纹

探究 'Performance analysis of a counter-flow indirect evaporative cooling system' 的科研主题。它们共同构成独一无二的指纹。

引用此