跳到主要导航 跳到搜索 跳到主要内容

Partial discharge location in power transformers using wideband RF detection

  • Zhiguo Tang
  • , Chengrong Li
  • , Xu Cheng
  • , Wei Wang
  • , Jinzhong Li
  • , Jun Li
  • North China Electric Power University

科研成果: 期刊稿件 › 文章 › 同行评审

111 引用 (Scopus)

摘要

This paper presents a method for partial discharge (PD) source location in power transformers based on detecting electromagnetic (EM) radiation emitted from PD. The key problem of PD location by EM waves is the difficulty in getting the accurate time arrivals of the signals from the source to multiple sensors. Several measures are taken to improve the time arrival resolution. Firstly, a measuring frequency band (1 GHz - 5 GHz) within RF band is proposed to accurately pick up the fast rise time of the signals. Secondly, an antenna array with diamond-shaped configuration is designed to improve the correlation coefficient of the waveforms from multiple sensors. Thirdly, two antenna arrays are proposed to eliminate the influences of the EM wave scattering caused by the iron core. Fourthly, an algorithm is proposed to increase the signal to noise radio and to measure the time arrivals automatically through cross-correlation and averaging operation. Lastly, a Hyperboloid-Genetic algorithm is developed to search the PD source. Experiments on a single-phase transformer model were conducted in the laboratory. The tested results proved the validity of the proposed method and showed that the location error in 16 cm, mostly is about several cm.

源语言英语
页(从-至)1193-1199
页数7
期刊IEEE Transactions on Dielectrics and Electrical Insulation
卷13
期6
DOI
出版状态已出版 - 12月 2006
已对外发布是

学术指纹

探究 'Partial discharge location in power transformers using wideband RF detection' 的科研主题。它们共同构成独一无二的学术指纹。

引用此