TY - JOUR
T1 - Partial discharge localisation methodology for power transformers based on improved acoustic propagation route search algorithm
AU - Wang, Yan Bo
AU - Fan, Yu Hang
AU - Qin, Shao Rui
AU - Chang, Ding Ge
AU - Shao, Xian Jun
AU - Mu, Hai Bao
AU - Zhang, Guan Jun
N1 - Publisher Copyright:
© 2018, The Institution of Engineering and Technology.
PY - 2018/11/1
Y1 - 2018/11/1
N2 - The localisation of partial discharge (PD) sources using the acoustic emission (AE) technique has attracted increasing research attention. The complicated propagation routes and wave-type conversion in power transformer can induce considerable localisation error. In this paper, the catadioptric phenomenon of AE wave propagation is explained in detail. With the incident angle varying, the wave type of the direct wave in tank wall could convert and the velocity will change accordingly. A transformer model is established in which each node refers to a suspected PD position and a shortest route search algorithm is proposed to calculate the shortest path between two nodes in this model. However, the fastest route is most significant to PD localisation rather than the shortest route when TDOA method is used. As a result, an improved propagation route search (IPRS) algorithm, which can recreate the propagation process and calculate the fastest AE routes, is proposed to localise the PD origin. To verify the feasibility of the IPRS algorithm, localisation experiments were performed in 35 and 110 kV transformers, respectively. Compared with other present localisation methods, such as the Chan algorithm, the genetic algorithm and the imperial competitive algorithm, the proposed algorithm can effectively reduce localisation error.
AB - The localisation of partial discharge (PD) sources using the acoustic emission (AE) technique has attracted increasing research attention. The complicated propagation routes and wave-type conversion in power transformer can induce considerable localisation error. In this paper, the catadioptric phenomenon of AE wave propagation is explained in detail. With the incident angle varying, the wave type of the direct wave in tank wall could convert and the velocity will change accordingly. A transformer model is established in which each node refers to a suspected PD position and a shortest route search algorithm is proposed to calculate the shortest path between two nodes in this model. However, the fastest route is most significant to PD localisation rather than the shortest route when TDOA method is used. As a result, an improved propagation route search (IPRS) algorithm, which can recreate the propagation process and calculate the fastest AE routes, is proposed to localise the PD origin. To verify the feasibility of the IPRS algorithm, localisation experiments were performed in 35 and 110 kV transformers, respectively. Compared with other present localisation methods, such as the Chan algorithm, the genetic algorithm and the imperial competitive algorithm, the proposed algorithm can effectively reduce localisation error.
UR - https://www.scopus.com/pages/publications/85055903081
U2 - 10.1049/iet-smt.2018.5092
DO - 10.1049/iet-smt.2018.5092
M3 - 文章
AN - SCOPUS:85055903081
SN - 1751-8822
VL - 12
SP - 1023
EP - 1030
JO - IET Science, Measurement and Technology
JF - IET Science, Measurement and Technology
IS - 8
ER -