TY - JOUR
T1 - Oil-paper insulation breakdown characteristics under non-standard lightning impulse voltages
AU - Wang, Zhe
AU - Zhang, Qiaogen
AU - Wang, Tonglei
AU - Li, Jinzhong
PY - 2014/9/30
Y1 - 2014/9/30
N2 - The non-standard lightning impulse voltages have variable front times, duration and possible high-frequency components superimposed in the waveform due to the reflection in the substation and other factors. These surges propagating into transformer windings may cause resonance and excite high potential gradient, and consequently leads to the breakdown of the windings' insulation. Hence, we investigated the impact of lightning impulse's front time and oscillation frequency on the breakdown characteristics using two electrode models to simulate the typical insulation configuration of windings in oil-immersed transformers. The experimental results indicate that the breakdown voltage increases with the decrease of front time, for example, the U50% under 0.25 µs steep front impulse voltage is 10%~17% higher than that under standard lightning impulse. For turn-to-turn insulation, its time lag is greatly influenced by the thickness of insulation layer and front time, while this time lag gets more sensitive to the front time with the increase of the number of insulation layers. The turn-to-turn insulation can withstand much more severe oscillation lightning impulse in comparison to standard lightning impulse, and its U50% increases with the oscillation frequency, from instance the U50% under an oscillation lightning impulse of 335 kHz is 25% higher than that under standard lightning impulse. Furthermore, while the total insulation paper thickness of turn-to-turn remains the same, increasing the layer number will raise the breakdown voltage of insulation.
AB - The non-standard lightning impulse voltages have variable front times, duration and possible high-frequency components superimposed in the waveform due to the reflection in the substation and other factors. These surges propagating into transformer windings may cause resonance and excite high potential gradient, and consequently leads to the breakdown of the windings' insulation. Hence, we investigated the impact of lightning impulse's front time and oscillation frequency on the breakdown characteristics using two electrode models to simulate the typical insulation configuration of windings in oil-immersed transformers. The experimental results indicate that the breakdown voltage increases with the decrease of front time, for example, the U50% under 0.25 µs steep front impulse voltage is 10%~17% higher than that under standard lightning impulse. For turn-to-turn insulation, its time lag is greatly influenced by the thickness of insulation layer and front time, while this time lag gets more sensitive to the front time with the increase of the number of insulation layers. The turn-to-turn insulation can withstand much more severe oscillation lightning impulse in comparison to standard lightning impulse, and its U50% increases with the oscillation frequency, from instance the U50% under an oscillation lightning impulse of 335 kHz is 25% higher than that under standard lightning impulse. Furthermore, while the total insulation paper thickness of turn-to-turn remains the same, increasing the layer number will raise the breakdown voltage of insulation.
KW - Front time
KW - Non-standard lightning impulse voltages
KW - Oil-immersed transformer
KW - Oil-pressboard insulation
KW - Oscillation frequency
KW - Turn-to-turn insulation
UR - https://www.scopus.com/pages/publications/84907953405
U2 - 10.13336/j.1003-6520.hve.2014.09.044
DO - 10.13336/j.1003-6520.hve.2014.09.044
M3 - 文章
AN - SCOPUS:84907953405
SN - 1003-6520
VL - 40
SP - 2931
EP - 2937
JO - Gaodianya Jishu/High Voltage Engineering
JF - Gaodianya Jishu/High Voltage Engineering
IS - 9
ER -