Numerical study on an air-cooling and liquid-cooling combined server for high-temperature data center application

  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

22 引用 (Scopus)

摘要

Liquid cooling is a promising energy-saving technology for data center cooling. The fluid flow and heat transfer characteristics of a novel air-cooling and liquid-cooling combined server (ALCS) are studied in this paper. The ALCS is modeled based on a 2U server with two CPU-packages, and the two-layered microchannel cold plates are adopted for the cooling of CPU-packages, while the fans are retained for the cooling of other low-power components (hard disk drive (HDD), memories, power units, and mother PCB board). The effects of fans rotation speed (FRS), water flow rate (WFR), and coolant inlet temperatures on the ALCS cooling performance are numerically studied. When air/water inlet temperatures and WFR are fixed (26.85 °C, 26.85 °C, and 0.24 L·min−1), the FRS can be reduced to 500 rad·s−1 under the condition that the limit temperature of components is not exceeded, and the total fans power is only 0.64 W for the server. When the inlet air/water temperature is constant, the cooling of CPU chips is mainly influenced by the WFR, while the cooling of HDDs, memories, and power units is mainly influenced by the FRS. When the air/water inlet temperatures are high (45 °C), the maximum temperature of HDDs and CPU chips is the main barrier to reducing FRS and WFR. By adjusting the FRS and WFR with fixed steps, an optimized ALCS working condition is obtained (FRS = 800 rad·s−1, WFR = 0.264 L·min−1), in which the maximum temperatures of CPU chips, HDDs, memories, and power units are respectively 84.36 °C, 59.73 °C, 84.83 °C, and 84.25 °C, while the total fans power is 2.427 W and the water pumping power is 0.657 mW. The ALCS proposed in this paper achieves effective and energy-saving cooling performance and shows the potential of safe operation under the high-temperature DC environment.

源语言英语
期刊论文编号128111
期刊Applied Thermal Engineering
卷280
DOI
出版状态已出版 - 1 12月 2025

学术指纹

探究 'Numerical study on an air-cooling and liquid-cooling combined server for high-temperature data center application' 的科研主题。它们共同构成独一无二的学术指纹。

引用此