跳到主要导航 跳到搜索 跳到主要内容

Numerical simulation of SF6 ARC characteristics influenced by electrode erosion

  • J. Zhang
  • , S. Jia
  • , X. Li
  • , Z. Shi
  • , L. Wang
  • Xi'an Jiaotong University

科研成果: 书/报告/会议事项章节 › 会议稿件 › 同行评审

2 引用 (Scopus)

摘要

During the interruption process of SF6 circuit breaker, electrode erosion will occur inevitably, which leads to the contamination of pure SF6 and the alteration of arc characteristics. In the paper, to one puffer type circuit breaker, simulation studies are focused on the application of Spalart-Allmaras model for turbulence and species transport model for metallic vapour diffusion. In addition, the electrode erosion rate is estimated by the energy balance processes at the arc and electrode interface. It demonstrates that the metallic vapour has cooling effects especially at the region close to upstream electrode, and the arc voltage is less sensitive to electrode erosion at lower current.

源语言英语
主期刊名GD 2008 - 17th International Conference on Gas Discharges and Their Applications
页205-208
页数4
出版状态已出版 - 2008
活动17th International Conference on Gas Discharges and Their Applications, GD 2008 - Cardiff, 英国
期限: 7 9月 2008 → 12 9月 2008

丛书

姓名GD 2008 - 17th International Conference on Gas Discharges and Their Applications

会议

会议17th International Conference on Gas Discharges and Their Applications, GD 2008
国家/地区英国
市Cardiff
时期7/09/08 → 12/09/08

学术指纹

探究 'Numerical simulation of SF6 ARC characteristics influenced by electrode erosion' 的科研主题。它们共同构成独一无二的学术指纹。

引用此