跳到主要导航 跳到搜索 跳到主要内容

Numerical Simulation of Environmental Control for Relics Preservation in the Funerary Pit by Air Curtain System

  • Xi'an Jiaotong University
  • Shaanxi Ener. Environmental and Building Energy Conservation Engineering Technology Re-search Center
  • China United Northwest Institute for Engineering Design and Research

科研成果: 期刊稿件 › 会议文章 › 同行评审

4 引用 (Scopus)

摘要

The air pollution and fluctuation of environmental parameters are the main causes of desiccation cracking, efflorescence of relics in archaeology museum. In this research, an air curtain system was proposed to separate the local environment in funerary pit from the large-space exhibition hall. An investigation of the air curtain was carried out to evaluate the integrated performance and to obtain the optimal jet elevation and velocity of the air curtain. The results show that the optimal jet elevation and jet velocity of the air curtain system were 3° and 5.5m/s, respectively. The preservation environment in the funerary pit can be greatly improved by the air curtain, the temperature difference between the top and bottom of funerary pit could be reduced to only 0.2°C. Moreover, the isolation efficiency of the air curtain system can reach to 89%.

源语言英语
页(从-至)265-272
页数8
期刊Procedia Engineering
卷205
DOI
出版状态已出版 - 2017
活动10th International Symposium on Heating, Ventilation and Air Conditioning, ISHVAC 2017 - Jinan, 中国
期限: 19 10月 2017 → 22 10月 2017

学术指纹

探究 'Numerical Simulation of Environmental Control for Relics Preservation in the Funerary Pit by Air Curtain System' 的科研主题。它们共同构成独一无二的学术指纹。

引用此