跳到主要导航 跳到搜索 跳到主要内容

Numerical and experimental analysis on indoor thermal environment in commercial kitchen

  • Jiangxi University of Science and Technology
  • Xi'an University of Architecture and Technology

科研成果: 书/报告/会议事项章节 › 会议稿件 › 同行评审

1 引用 (Scopus)

摘要

It is of great importance to study the impact of the cooking generated contaminants on the indoor air quality in the kitchen since cooking is regarded as the main source of indoor contaminants. This study aims investigate and analysis the indoor air quality of kitchen with using CFD numerical analysis method via the velocity, temperature, humidity CO 2 concentration .It is concluded that The temperature distribution are large difference in the kitchen and the maximum value is up to 324K on the work area which near the cooking ,and the CO 2 concentration which is close to the stove is 1420ppm,1370ppm, 1470ppm respectively, and it is more than the acceptance criteria (CO 2<1000ppm) 42%,37% and 47% respectively. It is serious impact on the staff's physical health.

源语言英语
主期刊名Advances in Environmental Science and Engineering
页4435-4438
页数4
DOI
出版状态已出版 - 2012
活动1st International Conference on Energy and Environmental Protection, ICEEP 2012 - Hohhot, 中国
期限: 23 6月 2012 → 24 6月 2012

丛书

姓名Advanced Materials Research
卷518-523
ISSN(印刷版)1022-6680

会议

会议1st International Conference on Energy and Environmental Protection, ICEEP 2012
国家/地区中国
市Hohhot
时期23/06/12 → 24/06/12

学术指纹

探究 'Numerical and experimental analysis on indoor thermal environment in commercial kitchen' 的科研主题。它们共同构成独一无二的学术指纹。

引用此