摘要
The existing priority-based current limiting control (CLC) for grid-forming (GFM) inverters may lead to failures in fault recovery, including being locked in CLC and mode oscillation between CLC and constant voltage control (CVC). To resolve these problems, this letter first reveals the fault recovery mechanism of droop controlled GFM inverters by illustrating the conditions of three fault recovery states in the phasor diagram. Then, two methods including determination of the optimal range of current angle and upper limit of saturation block are presented to guarantee successful fault recovery of GFM inverters. The correctness of theoretical analyses is verified and validated by multiple experimental tests.