跳到主要导航 跳到搜索 跳到主要内容

Measurement of transient electromagnetic coupling and interference caused by disconnector operation in substation

  • Wang Lihui
  • , Huang Jiayu
  • , Ji Jianfei
  • , Pang Fubin
  • , Yuan Yubo
  • Southeast University, Nanjing
  • Jiangsu Electric Power Company Research Institute

科研成果: 期刊稿件 › 文章 › 同行评审

8 引用 (Scopus)

摘要

Disconnector operation in the substation can cause transient electromagnetic disturbance and very fast transient over-voltage (VFTO), and will lead to the misoperation or damage of electrical protection system. To research the characteristics and influence of electromagnetic interference, principle of disconnector operation was analyzed. Then, an improved Agrawal model was adopted to describe the transmission line coupling process of disconnector operation, and telegraph equation was calculated by finite-difference time-domain (FDTD) method. With the model and method, the conduction process and characteristics of transient electromagnetic coupling and interference caused by disconnector operation in substation were simulated. Besides, disturbance voltage signal on the secondary cables caused by disconnector operation was measured in a 500 kV substation. Finally, parameters of transient electromagnetic coupling and interference in time domain and frequency domain were calculated respectively. Experiment results show that the quantitative level of transient electromagnetic coupling and interference caused by disconnector operation in substation can be evaluated in theory, and the core frequency points concerned in secondary circuit can be calculated.

源语言英语
页(从-至)1-7
页数7
期刊Measurement: Journal of the International Measurement Confederation
卷96
DOI
出版状态已出版 - 1 1月 2017
已对外发布是

学术指纹

探究 'Measurement of transient electromagnetic coupling and interference caused by disconnector operation in substation' 的科研主题。它们共同构成独一无二的学术指纹。

引用此