摘要
Convective mass transfer for the cross flow of air with water film outside the tube wall is analyzed for an indirect evaporative cooler with a horizontal tube. Experimental correlation is established for the convective mass transfer coefficient and shows that applying the Lewis relation to calculate the convective mass transfer coefficient is not accurate with discrepancies ranging from 70% to 160%.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 68-71 |
| 页数 | 4 |
| 期刊 | Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University |
| 卷 | 33 |
| 期 | 3 |
| 出版状态 | 已出版 - 3月 1999 |
学术指纹
探究 'Mass transfer outside a horizontal tube for an indirect evaporative cooler' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver