跳到主要导航 跳到搜索 跳到主要内容

Low voltage ride through control of large direct-drive wind turbine with multiphase PMSG and hybrid three-level full-size converters

  • Xiangjun Zeng
  • , Hongtao Zhang
  • , Ying Li
  • , Yongbing Yang
  • , Xu Yang
  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

7 引用 (Scopus)

摘要

In the case of grid voltages dips, the wind power plants are demanded to keep connected to the grid, and to help the network recover from the fault. This paper focuses on the low voltage ride through (LVRT) control of large-scale wind energy system based usinga multiphase direct drive permanent magnet synchrony generator (PMSG) and three-level converters. The paper analyzes the impact of generator side rectifiers and grid side converters cased by symmetrical or asymmetrical voltage dip. In order to fulfill the LVRT requirement, the energy accumulated in the converters has to be reduced. A control approach is developed, which is implemented by resetting current command and adjusting the speed of PMSG. Finally, a time-domain computer simulation is done for the proposed system. Simulation results confirm the feasibility and validity of the proposed method.

源语言英语
页(从-至)23-29
页数7
期刊Dianli Xitong Zidonghua/Automation of Electric Power Systems
卷36
期11
DOI
出版状态已出版 - 10 6月 2012

学术指纹

探究 'Low voltage ride through control of large direct-drive wind turbine with multiphase PMSG and hybrid three-level full-size converters' 的科研主题。它们共同构成独一无二的学术指纹。

引用此