跳到主要导航 跳到搜索 跳到主要内容

Linear Time-Periodic theory-based novel stability analysis method for voltage-source converter under unbalanced grid conditions

  • Hanwen Gu
  • , Yueming Ji
  • , Hao Qi
  • , Xintong Liu
  • , Zaibin Jiao
  • , Yinan Xiang
  • , Jun Liu
  • Xi'an Jiaotong University
  • State Grid Shandong Electric Power Corporation Weifang Power Supply Company

科研成果: 期刊稿件文章同行评审

2 引用 (Scopus)

摘要

Small-signal stability analysis is essential for the safe operation and parameter design of power electronic-dominated grids. Unbalanced conditions introduce more frequency-coupling terms, which are unneglectable in the stability assessment. This paper proposes a novel Linear Time-Periodic (LTP) theory-based stability analysis method and focuses on grid-connected voltage-source converters (VSCs) without improved unbalancing controls. Firstly, the analysis of fundamental solutions of the LTP system reveals that each LTP mode is characterized by a unique damping factor and multiple oscillation frequencies, defined by LTP eigenvalues and related transformation vectors, i.e., (λi,Vi(t)). Then, a method for calculating (λi,Vi(t)) is proposed using the characteristic matrix of the Harmonic State-Space (HSS) model. An iterative sorting method based on the time-domain interpretation of HSS eigenvalues/eigenvectors is proposed to determine accurate (λi,Vi(t)) in the case of the minimum truncation order. Finally, generalized definitions and calculation methods of the widely used indicators for modal analysis are presented to assess system stability and guide the parameter design. Numerical and simulation results verify the proposed stability analysis method and indicate its advantages compared to the existing Floquet and HSS methods.

源语言英语
文章编号110197
期刊International Journal of Electrical Power and Energy Systems
161
DOI
出版状态已出版 - 10月 2024

学术指纹

探究 'Linear Time-Periodic theory-based novel stability analysis method for voltage-source converter under unbalanced grid conditions' 的科研主题。它们共同构成独一无二的指纹。

引用此