跳到主要导航 跳到搜索 跳到主要内容

Investigation of the optimal intermediate water temperature in a combined r134a and transcritical CO2 heat pump for space heating

  • Yulong Song
  • , Dongzhe Li
  • , Feng Cao
  • , Xiaolin Wang
  • Xi'an Jiaotong University
  • University of Tasmania

科研成果: 期刊稿件文章同行评审

31 引用 (Scopus)

摘要

In this paper, the effect of intermediate water temperature on the performance of a combined R134a and transcritical CO2 heat pump was studied theoretically and experimentally. The mathematical model was first validated using experimental data and then applied to analyze the performance of the combined system. The results show that there exists an optimal intermediate water temperature (water inlet temperature at the gas cooler) at which the combined system has the highest COP. This optimal intermediate water temperature varies with the ambient air temperature. Furthermore, the effect of intermediate water temperature on individual R134a and transcritical CO2 subsystems was investigated. The results show that both heating capacity and power consumption in the R134a subsystem increase as the intermediate water temperature increases. However, power consumption in the CO2 system drops slightly, and heating capacity reaches an optimal value as the intermediate water temperature increases from 15 to 32 °C under ambient air temperatures ranging from −20 to 7 °C.

源语言英语
页(从-至)10-24
页数15
期刊International Journal of Refrigeration
79
DOI
出版状态已出版 - 7月 2017

学术指纹

探究 'Investigation of the optimal intermediate water temperature in a combined r134a and transcritical CO2 heat pump for space heating' 的科研主题。它们共同构成独一无二的学术指纹。

引用此