A bus-bar protection principle based on instantaneous impedance is proposed, which makes the internal bus fault state equivalent to an inductance model and defines the instantaneous equivalent impedance and the instantaneous restraining impedance respectively. When an internal fault occurs, the instantaneous equivalent impedance is equal to the instantaneous restraining impedance, which is the resulted impedance of all parallel branches connected to the bus-bar and relatively small. When an external fault occurs, the instantaneous equivalent impedance is at least two times larger than the instantaneous restraining impedance no matter whether there is CT (Current Transformer) saturation. The external bus fault is thus easily distinguished from the internal fault and the protection acts quickly and properly. The bus-bar protection based on the proposed principle does not need to detect CT saturation and its protective criterion is immune to the transition resistance. It has clear tripping boundary and is suitable for different harmonic and non-periodic components. Its feasibility is verified by EMTP simulation.

源语言英语
页(从-至)6-12
页数7
期刊Dianli Zidonghua Shebei/Electric Power Automation Equipment
卷30
期8
出版状态已出版 - 8月 2010