摘要
The operating experience of SF6 gas insulated switchgear (GIS) shows that insulators are often the weak link and key factor of system' s insulation. Therefore it' s important to find out factors influencing flashover characteristics of insulators. Based on a steep-front impulse test device, this paper presents our study about the influence of surface conditions along insulators on their flashover characteristics. The results show that increasing the surface roughness would decrease the flashover voltage of insulators, and this phenomenon is analyzed from the perspective of surface absorption ability of insulators. Flashover voltage drops obviously when conductive particle is attached to insulator surface, and the closer the particle is to the high-voltage electrode, the lower flashover voltage becomes, which is due to the change of electric filed along insulator surface brought by the change of particle position.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 63-69 |
| 页数 | 7 |
| 期刊 | Gaoya Dianqi/High Voltage Apparatus |
| 卷 | 52 |
| 期 | 4 |
| DOI | |
| 出版状态 | 已出版 - 16 4月 2016 |
学术指纹
探究 'Influence of surface conditions on flashover characteristics of supporting insulators in GIS under lightning impulse' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver