In high voltage direct current (HVDC) system, the breakdown characteristics of oil paper insulation are significantly affected by its aging status and space charge effect. We used the accelerated thermal-aging treatment method to obtain three oil-paper insulation with different aging degrees, and injected the space charge by using pre-voltage with different amplitudes and measured their breakdown voltages. Then we used the pulsed electro-acoustic (PEA) method to observe the space charge distribution at room temperature and further analyzed internal electric field and trap distribution within sample. The experimental results show that the overall breakdown voltage of sample after 3 kV pre-voltage is higher than that of sample without pre-voltage treatment. The trap density increases with the aging degree of oil-paper, and the space charge quantity becomes larger, enhancing the space charge effect and breakdown voltage trend. However, the overall breakdown voltage of sample after 4 kV pre-voltage is lower than that of sample after 3 kV pre-voltage. Hence, special attention should be paid that the breakdown voltage of oil-paper insulation will reduce in actual operation when the amplitude of homopolarity pre-voltage exceeds a certain value.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 3066-3072 |
| 页数 | 7 |
| 期刊 | Gaodianya Jishu/High Voltage Engineering |
| 卷 | 41 |
| 期 | 9 |
| DOI | |
| 出版状态 | 已出版 - 30 9月 2015 |