摘要
In a dc distributed power system, the interaction between individually designed power modules/subsystems may cause the instability of the whole system. In a small-signal sense, system level stability is determined by the impedance ratio Z o/Z i. Here Z o is the output impedance of the source module/subsystem, and Z i is the input impedance of the load module/subsystem. As a result, an effective way to prevent system instability is defining impedance specifications for modules/subsystems. This paper briefly summarizes existing works and introduces our contribution in defining impedance specifications. A new forbidden region for impedance ratio Z o/Z i on the S-plane is proposed as the system stability margin requirement. Based on this proposed forbidden region, the impedance specifications of individual loads are established. Further, a very practical measurement approach is developed to examine whether or not the system stability margin requirement of the forbidden region is satisfied.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 157-162 |
| 页数 | 6 |
| 期刊 | IEEE Transactions on Power Electronics |
| 卷 | 17 |
| 期 | 2 |
| DOI | |
| 出版状态 | 已出版 - 3月 2002 |
| 已对外发布 | 是 |