摘要
As a common interface circuit for renewable energy integrated into the power grid, the inverter is prone to work under a three-phase unbalanced weak grid. In this paper, the instability of grid-connected inverters under the unbalanced grid condition is investigated. First, a dual second-order generalized integrator phase-locked loop (DSOGI-PLL)-based inverter under balanced and unbalanced conditions is modeled. A fourth-order impedance model is established to describe its impedance characteristics under the unbalanced grid condition. To analyze this multi-input multi-output system, a simplified stability analysis method based on the generalized Nyquist stability criterion and matrix theory is proposed. Then, the influences of circuit and control parameters on the stability of the grid-connected inverter system under the unbalanced grid condition are investigated. Finally, the accuracy of the derived frequency-coupled impedance model is verified via simulations, and the effectiveness of the proposed simplified stability analysis method on the system stability analysis is verified via both simulations and hardware experiments.
| 源语言 | 英语 |
|---|---|
| 文章编号 | 12441 |
| 期刊 | Applied Sciences (Switzerland) |
| 卷 | 13 |
| 期 | 22 |
| DOI | |
| 出版状态 | 已出版 - 11月 2023 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源
学术指纹
探究 'Impedance-Based Stability Analysis of Grid-Connected Inverters under the Unbalanced Grid Condition' 的科研主题。它们共同构成独一无二的指纹。引用此