Impact of overhead air supply layout on the thermal performance of a container data center

科研成果: 期刊稿件文章同行评审

7 引用 (Scopus)

摘要

This study focused on the improved designs of airflow management in container data centers having overhead air supply. The computational fluid dynamics (CFD) model is first validated with experimental results. Then, the impact of grille diameter, deflector angle, and air supply layout on the data center thermal performance is investigated. The results show that the larger grille diameter may reduce the volumetric flowrate through the upstream grille, causing insufficient air supply and strong hot-air recirculation at the first rack A1. By decreasing the grille diameter from 335mm to 235 mm, the average rack cooling index (RCI) and supply heat index (SHI) can be improved from 25.4% and 0.292 to 65% and 0.258, respectively. However, implementing small diameter grilles is not an economic way for data center performance improvement as far as the energy consumption is concerned due to the high pumping power. Meanwhile, raising the deflector angle below 30 deg in grille S1 can provide moderate improvement on temperature of the A1 rack. A further rise in the deflector to 40 deg may impose severe deterioration with a pronounced hot-spot area. The data center performance can be improved by changing from center-cold-aisle arrangement to center-hot-aisle layout. The layout provides much higher return air temperature and the RCI and SHI can be improved by 32.7% and 34.5%, respectively.

源语言英语
文章编号011008
期刊Journal of Electronic Packaging
142
1
DOI
出版状态已出版 - 3月 2020
已对外发布

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

学术指纹

探究 'Impact of overhead air supply layout on the thermal performance of a container data center' 的科研主题。它们共同构成独一无二的指纹。

引用此