摘要
Fully kinetic simulations of arc discharge in vacuum interrupters (VIs) often suffer from prohibitive computational costs. In this article, a hybrid kinetic-magnetohydrodynamic (MHD) transient simulation of vacuum arc using a field-circuit coupling method is proposed for a vacuum circuit breaker. Compared with the fully kinetic simulation method, the advance of the proposed method originates from the so-called hybrid modeling of ion kinetics and electron MHD, where ions and electrons in a VI are separately treated as macroparticles and massless fluids. The simulation results of the arc are consistent with the arc morphology in the discharge plasma experiment. Furthermore, the proposed field-circuit coupling transient model is used to study the number and the decay time of plasma between the electrodes during the interruption process. Finally, we discussed the dielectric-recovery characteristics and the breakdown probability under different voltage frequencies, voltage levels, and electrode gaps.
| 源语言 | 英语 |
|---|---|
| 期刊论文编号 | 8937072 |
| 期刊 | IEEE Transactions on Magnetics |
| 卷 | 56 |
| 期 | 1 |
| DOI | |
| 出版状态 | 已出版 - 1月 2020 |
学术指纹
探究 'Hybrid Kinetic-MHD Simulations of Vacuum Arc Using Field-Circuit Coupling Method' 的科研主题。它们共同构成独一无二的学术指纹。引用此