HVDC换相失败时受端电网的电压与频率联合控制策略

  • Yan Cheng
  • , Jian Zhang
  • , Ti Guan
  • , Shumin Sun
  • , Linbo Yu
  • , Peng Yu
  • , Nan Wang
  • , Shibo Wang
  • , Peng Kou
  • Shandong Electric Power Research Institute
  • Shandong Power Dispatching & Control Center
  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

12 引用 (Scopus)

摘要

Voltage and frequency support after commutation failure at receiving end of HVDC transmission system is studied in this paper. Commutation failures can cause temporary interruption of transmitted power, resulting in severe voltage and frequency deviation. In view of this, quick active and reactive power support is needed. To do this, a coordinated control strategy for combined system of synchronous condenser and energy storage is proposed and the coordination is achieved by setting reasonable control parameters. This strategy aims to provide fast substantive active and reactive power support, reducing the voltage nadir as well as speeding up the process of system recovery. The control strategy is tested through simulations and the results demonstrated the effectiveness of the proposed scheme.

投稿的翻译标题Coordinated Control Strategy of Voltage and Frequency Support at Receiving End of HVDC System Under Commutation Failure
源语言繁体中文
页(从-至)241-245
页数5
期刊Gaoya Dianqi/High Voltage Apparatus
56
4
DOI
出版状态已出版 - 16 4月 2020

关键词

  • DC commutation failure
  • Energy storage system
  • HVDC
  • Synchronous condenser