Generation process of impurity bridges in oil-paper insulation under DC voltage

  • Jinzhong Li
  • , Qiaogen Zhang
  • , Yuan Li
  • , Tonglei Wang
  • , Heli Ni
  • State Grid Corporation of China
  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

33 引用 (Scopus)

摘要

The valve-side windings of converter transformers have to endure combined AC-DC voltage in operation. Under DC voltage, solid impurities generated due to PD (partial discharge) may cause great threat to the insulating ability of oil-paper insulation. However, the generation and growth mechanism of solid impurities is still unavailable. In this paper, an oil-paper insulation model was established and the content of micro impurity bridges was analyzed. The generation and growth process of micro impurity bridges under negative DC voltage were investigated. Besides, PD characteristics during the above process were also acquired synchronously. The experimental results show that micro bridge impurities are formed by fiber bundles detached from the surface of the insulating paper under DC electric field. The generation and growth process of micro impurity bridges can be divided into three stages. Among the stages the quantity of micro bridges increases significantly. The diameter of the bridge increases from 100 μm in the first stage to 1 mm in the third stage, along with which is the increase of the PD average charge from 400 pC to 1 000 pC and the PDs rates from dozens to hundreds per minute. At the third stage a 'hazardous bridge' emerges, leading to the final breakdown of the insulation. Besides, a 'cluster discharging' phenomenon appears in the second stage, which is associated with the generation and the disappearance of micro bridge impurities.

源语言英语
页(从-至)3901-3908
页数8
期刊Gaodianya Jishu/High Voltage Engineering
42
12
DOI
出版状态已出版 - 31 12月 2016

学术指纹

探究 'Generation process of impurity bridges in oil-paper insulation under DC voltage' 的科研主题。它们共同构成独一无二的学术指纹。

引用此