跳到主要导航 跳到搜索 跳到主要内容

Film condensing heat transfer of R134a on single horizontal tube coated with open cell copper foam

  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

34 引用 (Scopus)

摘要

Film condensing of refrigerant R134a on single horizontal tube coated with open cell copper foam was investigated at saturation pressures of 10.1 Bar and 8.87 Bar. Two foam thicknesses of 1.6 and 2.5 mm, three pore densities of 40, 80 and 130 PPI(Pores per inch) as well as the porosity of 90%, characterize the six tubes in the experiment. Heat flux in this work ranges from 10 to 60 kW/m2. It is found that saturation vapor pressure within the measurement range has almost no effect on the condensing heat transfer in the range of 8.87-10.1 Bar. Film condensing depends much on foam thickness with the pore density of 40 PPI, compared with 80 PPI and 130 PPI. The heat transfer coefficient generally ranges from 2 to 6 kW/m2 K for the six tubes, which decreases linearly up to the heat flux of 60 kW/m2 on a log-log plot. The enhanced ratio of all the coated tubes compared with that of the plain tube ranges from 2 to 3. Minor increment of the enhanced ratio is observed as the increment of heat flux.

源语言英语
页(从-至)335-343
页数9
期刊Applied Thermal Engineering
76
DOI
出版状态已出版 - 5 2月 2015

学术指纹

探究 'Film condensing heat transfer of R134a on single horizontal tube coated with open cell copper foam' 的科研主题。它们共同构成独一无二的学术指纹。

引用此