TY - JOUR
T1 - Fault-Tolerant Control of CPS-PWM-Based Cascaded Multilevel Inverter with Faulty Units
AU - Xiong, Liansong
AU - Zhuo, Fang
AU - Liu, Xiaokang
AU - Xu, Zhao
AU - Zhu, Yixin
N1 - Publisher Copyright:
© 2013 IEEE.
PY - 2019
Y1 - 2019
N2 - Bypassing the faulty power unit(s) of the regenerative cascaded multilevel inverter (CMI) directly results in a series of adverse influences. The existing solutions are not easy to implement and only effective for the Y-connected devices composed of regenerative CMIs. To bypass the faulty power units seamlessly, the corresponding control strategies must guarantee: 1) constant equivalent switching frequency; 2) constant sampling frequency; and 3) constant fundamental voltage amplitude. To this end, a generic fault-tolerant control strategy, which adjusts the carrier frequency and simultaneously changes the CMI dc voltage and/or the modulation ratio, is presented in this paper. It is applicable for the device composed of carrier phase-shifting pulsewidth modulation (CPS-PWM)-based CMIs to ride through faults seamlessly, whether it is a single-phase system, a three-phase system (being it δ -connected or Y-connected), or a multiphase system. The detailed implementation is also analyzed by modeling the output voltage of the CPS-PWM-based CMI. The experimental results verify the validity and superiority of the proposed fault-tolerant strategy for the CPS-PWM-based CMI system with faulty power units.
AB - Bypassing the faulty power unit(s) of the regenerative cascaded multilevel inverter (CMI) directly results in a series of adverse influences. The existing solutions are not easy to implement and only effective for the Y-connected devices composed of regenerative CMIs. To bypass the faulty power units seamlessly, the corresponding control strategies must guarantee: 1) constant equivalent switching frequency; 2) constant sampling frequency; and 3) constant fundamental voltage amplitude. To this end, a generic fault-tolerant control strategy, which adjusts the carrier frequency and simultaneously changes the CMI dc voltage and/or the modulation ratio, is presented in this paper. It is applicable for the device composed of carrier phase-shifting pulsewidth modulation (CPS-PWM)-based CMIs to ride through faults seamlessly, whether it is a single-phase system, a three-phase system (being it δ -connected or Y-connected), or a multiphase system. The detailed implementation is also analyzed by modeling the output voltage of the CPS-PWM-based CMI. The experimental results verify the validity and superiority of the proposed fault-tolerant strategy for the CPS-PWM-based CMI system with faulty power units.
KW - Carrier phase-shifting pulsewidth modulation (PWM)
KW - fault-tolerant control
KW - faulty power units
KW - regenerative cascaded multilevel inverter (CMI)
KW - static synchronous compensator (STATCOM)
UR - https://www.scopus.com/pages/publications/85077491459
U2 - 10.1109/JESTPE.2019.2898907
DO - 10.1109/JESTPE.2019.2898907
M3 - 文章
AN - SCOPUS:85077491459
SN - 2168-6777
VL - 7
SP - 2486
EP - 2497
JO - IEEE Journal of Emerging and Selected Topics in Power Electronics
JF - IEEE Journal of Emerging and Selected Topics in Power Electronics
IS - 4
M1 - 8640124
ER -