TY - JOUR
T1 - Experimental study on water boiling heat transfer characteristics of microchannel surface in distributed jet array impingement with effusion slots
AU - Tang, Xiaoyu
AU - Xu, Qiang
AU - Yu, Haoyuan
AU - Pei, Chenyu
AU - Guo, Liejin
N1 - Publisher Copyright:
© 2024 Elsevier Inc.
PY - 2025/3
Y1 - 2025/3
N2 - Distributed jet array impingement can improve the uneven temperature distribution and achieve high heat flux cooling. This paper experimentally investigated the two-phase heat transfer and pressure drop characteristics in a distributed jet array impingement on the microchannel surface. The test operating conditions were mass flux of 100 ∼ 200 kg/m2s, subcooling degree of 20 ∼ 40 K, jet-to-target spacing of 2 ∼ 4 mm, and atmospheric pressure at the outlet. The experimental results show that lowering subcooling from 40 K to 20 K enhances the heat transfer coefficient between 45.4 % and 57.2 % and a growth in the average pressure drop of 25.5 %. Increasing mass flux causes inlet and outlet pressure to fluctuate more sharply due to enhanced condensation. The pressure drop of single-phase forced convection and that of two-phase nucleated boiling display an opposite trend as mass flux increases. Reducing jet-to-target spacing to 2 mm exhibits a noticeable enhancement in pressure drop of more than 2.5 times, and the standard deviation of inlet pressure declines instead, indicating that decreasing jet-to-target spacing can attenuate flow instability. The coefficient of performance can be raised by increasing subcooling and jet-to-target spacing and reducing mass flux in the whole heat flux range. Expanding jet-to-target spacing from 2 mm to 4 mm can produce 105.5 % to 141.7 % higher the average coefficient of performance.
AB - Distributed jet array impingement can improve the uneven temperature distribution and achieve high heat flux cooling. This paper experimentally investigated the two-phase heat transfer and pressure drop characteristics in a distributed jet array impingement on the microchannel surface. The test operating conditions were mass flux of 100 ∼ 200 kg/m2s, subcooling degree of 20 ∼ 40 K, jet-to-target spacing of 2 ∼ 4 mm, and atmospheric pressure at the outlet. The experimental results show that lowering subcooling from 40 K to 20 K enhances the heat transfer coefficient between 45.4 % and 57.2 % and a growth in the average pressure drop of 25.5 %. Increasing mass flux causes inlet and outlet pressure to fluctuate more sharply due to enhanced condensation. The pressure drop of single-phase forced convection and that of two-phase nucleated boiling display an opposite trend as mass flux increases. Reducing jet-to-target spacing to 2 mm exhibits a noticeable enhancement in pressure drop of more than 2.5 times, and the standard deviation of inlet pressure declines instead, indicating that decreasing jet-to-target spacing can attenuate flow instability. The coefficient of performance can be raised by increasing subcooling and jet-to-target spacing and reducing mass flux in the whole heat flux range. Expanding jet-to-target spacing from 2 mm to 4 mm can produce 105.5 % to 141.7 % higher the average coefficient of performance.
KW - Coefficient of performance
KW - Distributed jet array impingement
KW - Heat transfer
KW - Jet-to-target spacing
KW - Microchannel surface
UR - https://www.scopus.com/pages/publications/85212121559
U2 - 10.1016/j.ijheatfluidflow.2024.109723
DO - 10.1016/j.ijheatfluidflow.2024.109723
M3 - 文章
AN - SCOPUS:85212121559
SN - 0142-727X
VL - 112
JO - International Journal of Heat and Fluid Flow
JF - International Journal of Heat and Fluid Flow
M1 - 109723
ER -