摘要
The effect of the discharge pressure on the performance of the trans-critical CO2 heat pump with a low gas-cooler outlet temperature is experimentally investigated on a test rig of water source heat-pump water heater. The optimal discharge pressure of the trans-critical CO2 heat pump is investigated under different external operation conditions. When the tap-water temperature is low, the characteristic of the S-shape isotherm at the supercritical region has little effect on the occurrence of the optimal discharge pressure; while the mass flow rate of CO2, the suction pressure and the gas-cooler outlet temperature play a significant role in determining the emergence of the optimal discharge pressure. At the optimal discharge pressure, the COP reaches the peak; however, the corresponding heating capacity is still lower than its maximum, which is reached as the discharge pressure is slightly above the optimal discharge pressure. Reducing the tap-water flowrate or increasing the water-source temperature can increase the optimal discharge pressure. The COP is positively dependent on both the tap-water flowrate and the water-source temperature. In addition, the tap-water flowrate has a negligible influence on the maximum heating capacity while increasing the water-source temperature can greatly enhance the heating capacity.
| 源语言 | 英语 |
|---|---|
| 期刊论文编号 | 810 |
| 期刊 | Energies |
| 卷 | 10 |
| 期 | 6 |
| DOI | |
| 出版状态 | 已出版 - 1 6月 2017 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源
学术指纹