摘要
It is very important that a GIS on-line detecting system is built availably, and it is also the key to acquiring successful detection. And it is of great significance to find out which parts are liable to faults as well as their real discharge characteristics. By using an ultra-wideband partial discharge detecting system, the discharge signal from disk-type spacer in key part of 110kV GIS is acquired and studied. These key parts are the part nearby PT, the part nearby CT, the part nearby CB, the part nearby bus, the part nearby the LA. According to the different machine structure and electromagnetic field non-uniform distribution, these disk-spacers have different partial discharge characteristics. It is found that spacers in different parts of GIS have their own partial discharge characteristics, and their discharge frequencies concentrate below 300MHz, which provide numerical reference for the on-line monitoring of GIS.
| 源语言 | 英语 |
|---|---|
| 页 | 691-693 |
| 页数 | 3 |
| 出版状态 | 已出版 - 2005 |
| 活动 | 2005 International Symposium on Electrical Insulating Materials, ISEIM 2005 - Kitakyushu, 日本 期限: 5 6月 2005 → 9 6月 2005 |
会议
| 会议 | 2005 International Symposium on Electrical Insulating Materials, ISEIM 2005 |
|---|---|
| 国家/地区 | 日本 |
| 市 | Kitakyushu |
| 时期 | 5/06/05 → 9/06/05 |
学术指纹
探究 'Experimental study on the partial discharge characteristics of the disk-spacers in different parts of GIS in service' 的科研主题。它们共同构成独一无二的指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver