摘要
Experimental investigation on the R134-a spray cooling characteristics is presented in a closed loop system. A full-cone nozzle was applied to spray onto a heated circular copper plate. The characteristics of the R134-a spray cooling under a series of different volumetric flow rate were obtained. The results shown that volumetric flow rate improves the critical heat flux (CHF). And larger volumetric flow rate prevent the dry-out phenomenon under high heat flux. However, volumetric flow rate bring the adverse condition that reduces the system efficiency. The maximum CHF of 117.2Wcm-2 was achieved with 319K target surface temperature at 0.356Lmin-1. The results indicate that R134-a owns a great cooling characteristics in spray cooling system.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 194-200 |
| 页数 | 7 |
| 期刊 | Experimental Thermal and Fluid Science |
| 卷 | 61 |
| DOI | |
| 出版状态 | 已出版 - 1 2月 2015 |
学术指纹
探究 'Experimental study on the characteristics of a closed loop R134-a spray cooling' 的科研主题。它们共同构成独一无二的指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS