TY - JOUR
T1 - Experimental study on boiling heat transfer and pressure drop characteristics of hybrid jet microchannel heat sink
AU - Tang, Xiaoyu
AU - Xu, Qiang
AU - Yu, Haoyuan
AU - Pei, Chenyu
AU - Guo, Liejin
N1 - Publisher Copyright:
© 2024 Elsevier Ltd
PY - 2025/2/15
Y1 - 2025/2/15
N2 - Hybrid jet microchannel cooling can improve the non-uniform temperature distribution, significant pressure drop in microchannel, and the uneven heat transfer coefficient in jet impact. The heat transfer and pressure drop characteristics of a hybrid jet microchannel heat sink were investigated experimentally using deionized water as the working fluid. The experiments were carried out under the operating conditions of mass fluxes from 200 ∼ 600 kg/m2s, subcooling degrees from 20 ∼ 40 K, jet-to-target spacings from 1 ∼ 2.5 mm, and outlet pressure of 1 atm. The results show that increasing jet-to-target spacing and mass flux and decreasing subcooling can improve the heat transfer coefficient, and the maximum heat transfer coefficients increase by 58 %, 73 %, and 50 %, respectively. A heat transfer correlation for the hybrid jet microchannel is proposed with a mean absolute error of 6.5 % based on the experimental data. Since large jet-to-target spacing has more expansion space and is closer to the length of the potential core, increasing jet-to-target spacing results in higher critical heat flux at low mass flux. Compared to the heat sink with higher jet-to-target spacing, the pressure drop of the heat sink with the lower one is significantly affected by the mass flux due to the superposition of size effect of the channel and gas–liquid friction. In addition, the slope that pressure drop curves increase with the decrease of jet-to-target spacing rises with the mass flux, while it is not apparent with the subcooling. As the subcooling and jet-to-target spacing rise and the mass flux decreases, the coefficient of performance will increase.
AB - Hybrid jet microchannel cooling can improve the non-uniform temperature distribution, significant pressure drop in microchannel, and the uneven heat transfer coefficient in jet impact. The heat transfer and pressure drop characteristics of a hybrid jet microchannel heat sink were investigated experimentally using deionized water as the working fluid. The experiments were carried out under the operating conditions of mass fluxes from 200 ∼ 600 kg/m2s, subcooling degrees from 20 ∼ 40 K, jet-to-target spacings from 1 ∼ 2.5 mm, and outlet pressure of 1 atm. The results show that increasing jet-to-target spacing and mass flux and decreasing subcooling can improve the heat transfer coefficient, and the maximum heat transfer coefficients increase by 58 %, 73 %, and 50 %, respectively. A heat transfer correlation for the hybrid jet microchannel is proposed with a mean absolute error of 6.5 % based on the experimental data. Since large jet-to-target spacing has more expansion space and is closer to the length of the potential core, increasing jet-to-target spacing results in higher critical heat flux at low mass flux. Compared to the heat sink with higher jet-to-target spacing, the pressure drop of the heat sink with the lower one is significantly affected by the mass flux due to the superposition of size effect of the channel and gas–liquid friction. In addition, the slope that pressure drop curves increase with the decrease of jet-to-target spacing rises with the mass flux, while it is not apparent with the subcooling. As the subcooling and jet-to-target spacing rise and the mass flux decreases, the coefficient of performance will increase.
KW - Coefficient of performance
KW - Heat transfer
KW - Hybrid jet microchannel
KW - Jet-to-target spacing
KW - Pressure drop
UR - https://www.scopus.com/pages/publications/85210989819
U2 - 10.1016/j.applthermaleng.2024.125077
DO - 10.1016/j.applthermaleng.2024.125077
M3 - 文章
AN - SCOPUS:85210989819
SN - 1359-4311
VL - 261
JO - Applied Thermal Engineering
JF - Applied Thermal Engineering
M1 - 125077
ER -