Experimental investigations on the working performance of a sliding vane pump in the electronic direct cooling system

  • Xi'an Jiaotong University
  • University of Tasmania

科研成果: 期刊稿件文章同行评审

2 引用 (Scopus)

摘要

In the two-phase electronic direct cooling system, the traditional centrifugal pump often has low efficiency, and it heavily suffers from the cavitation problem. To deal with this problem, a sliding vane rotary pump was developed and tested in a two-phase electronic evaporative cooling system, and the working performance was investigated and analyzed based on the experimental data. The effect of the suction port size was studied. In a two-phase cooling system, the volumetric efficiency decreased with the rotary speed. The discharge valve had no fatal influence on the stable working performance of the pump. However, it highly affected the volumetric efficiency in high rotary speed while it acted insignificantly in the low speed. A stable cooling result could be quickly obtained during the change of the heat flux with the driving of the sliding vane pump, and a minor dependence between flow rates was detected, which was caused by the pressure rise. Therefore, the sliding vane pump was able to be an alternative pump for the two-phase electronic direct cooling system.

源语言英语
页(从-至)484-491
页数8
期刊Science and Technology for the Built Environment
26
4
DOI
出版状态已出版 - 20 4月 2020