跳到主要导航 跳到搜索 跳到主要内容

Experimental investigation on startup performances of a separator assisted two-phase loop thermosyphon

  • Nanjing Tech University

科研成果: 期刊稿件文章同行评审

23 引用 (Scopus)

摘要

In this study, visual experiment facilities of the two-phase loop thermosyphon with reservoir (RTLTP) and the separator assisted two-phase loop thermosyphon (STLTP) were established, and the startup performances of two systems, including the overshoot temperature, startup time and stabilized time were measured and compared. The results showed that compared with RTLTP, the stabilized time of STLTP was shorter about 420 s with less oscillation during startup process due to its lower pressure drop of fluid in the two-phase tube. The oscillation mechanism of fluid mass flow rate in RTLTP were analyzed. The reason for oscillation of fluid mass flow rate was because vapor generated in evaporator reversely flows back into the liquid tube and separator and the insufficient driven force. Furthermore, the effects of the charge, cooling water inlet temperature and heat load on the startup performances of two systems were studied as well.

源语言英语
文章编号119141
期刊International Journal of Heat and Mass Transfer
148
DOI
出版状态已出版 - 2月 2020

学术指纹

探究 'Experimental investigation on startup performances of a separator assisted two-phase loop thermosyphon' 的科研主题。它们共同构成独一无二的指纹。

引用此