跳到主要导航 跳到搜索 跳到主要内容

Experimental investigation on air-source transcritical CO2 heat pump water heater system at a fixed water inlet temperature

  • Xi'an Jiaotong University
  • University of Illinois at Urbana-Champaign

科研成果: 期刊稿件文章同行评审

191 引用 (Scopus)

摘要

For clarify main affecting factors on air-source transcritical CO 2 heat pump water heaters, and the influence extent of these main affecting factors, at fixed water inlet temperature of 12°C, an experimental research was conducted on a prototype in a range of ambient temperatures (-15°C-35°C) and water outlet temperatures (55°C-80°C). Based on the experimental results, effect of water outlet temperatures and ambient temperatures on the optimal discharge pressure and system COP was illustrated, and with change of water outlet temperatures and ambient temperatures, variation of CO2 gas cooler outlet temperatures, evaporating temperatures and other cycle variables was presented and interpreted. According established simulation model, we conducted simulation for the prototype and the cycle respectively adopted another two gas coolers with difference heat transfer surface. As one conclusion, for an established plant, correlation for the optimal discharge pressure as the function of ambient temperatures and water outlet temperatures can be achieved by fitting numerous simulation or experimental results.

源语言英语
页(从-至)701-716
页数16
期刊International Journal of Refrigeration
36
3
DOI
出版状态已出版 - 5月 2013

学术指纹

探究 'Experimental investigation on air-source transcritical CO2 heat pump water heater system at a fixed water inlet temperature' 的科研主题。它们共同构成独一无二的学术指纹。

引用此