跳到主要导航 跳到搜索 跳到主要内容

Experimental investigation of the optimal heat rejection pressure for a transcritical CO2 heat pump water heater

  • Xi'an Jiaotong University
  • Jiangsu Baixue Electric Appliances Co. Ltd.
  • University of Tasmania

科研成果: 期刊稿件文章同行评审

136 引用 (Scopus)

摘要

The system performance of a transcritical CO2 heat pump is significantly influenced by the heat rejection pressure due to the nature of the transcritical refrigeration cycle. It has received wide attention in the scientific community. In this article, an experimental investigation of the optimal heat rejection pressure for a transcritical CO2 heat pump water heater is presented. It is found that the optimal heat rejection pressure varies with gas-cooler outlet refrigeration temperature at different ambient temperatures. The further experimental results show that the Coefficient of Performance (COP) at the optimal heat rejection pressure decreases substantially with increasing gas-cooler outlet refrigeration temperature in a range from 25 to 45 °C. Based on the experimental data, a simple correlation of the optimal heat rejection pressure in terms of gas-cooler outlet refrigeration temperature is obtained. The analysis shows that the deviation of the correlation is within ±5%, and the predicted COP at the optimal heat rejection pressure is within 6%.

源语言英语
页(从-至)120-125
页数6
期刊Applied Thermal Engineering
56
1-2
DOI
出版状态已出版 - 2013

学术指纹

探究 'Experimental investigation of the optimal heat rejection pressure for a transcritical CO2 heat pump water heater' 的科研主题。它们共同构成独一无二的指纹。

引用此